| Pavilion Specifications |
PHV-50 |
PHV-70 |
PHV-100 |
PHV-140 |
| BTUH @ 190°F E.W.T. |
56,200 |
79,700 |
113,400 |
150,400 |
| BTUH @ 180°F E.W.T. |
52,300 |
73,800 |
105,000 |
138,200 |
| BTUH @ 170°F E.W.T. |
48,500 |
67,500 |
95,500 |
126,000 |
| BTUH @ 160°F E.W.T. |
44,400 |
62,900 |
86,300 |
113,800 |
| BTUH @ 150°F E.W.T. |
41,500 |
55,000 |
77,000 |
101,600 |
| BTUH @ 140°F E.W.T. |
37,500 |
49,500 |
68,700 |
89,500 |
| BTUH @ 130°F E.W.T. |
32,700 |
44,500 |
59,300 |
77,400 |
| BTUH @ 120°F E.W.T. |
29,500 |
38,000 |
49,600 |
65,300 |
| BTUH @ 110°F E.W.T. |
23,200 |
30,000 |
37,200 |
53,300 |
| Electrical Strip Heater |
5 - 15 Kw |
5 - 18 Kw |
5 - 23 Kw |
N/A |
| TX Cooling MBH1 |
18 - 24 |
30 - 36 |
42 - 60 |
60 |
| BTUH @ 44°F E.W.T. |
24,400 |
35,000 |
51,000 |
57,900 |
| BTUH @ 42°F E.W.T. |
26,000 |
37,800 |
55,000 |
62,900 |
| C.F.M. @ 1.5" E.S.P. |
550 |
750 |
1100 |
1250 |
| HP - RPM |
1/4 - 1625 |
1/3 - 1625 |
1/2 - 1625 |
3/4 - 1625 |
| AMPS @ 115/1/60 |
4.5 (High) |
5.0 |
7.5 |
8.5 |
| G.P.M. FLOW RATINGS |
5 |
7 |
10 |
10 |
| S/A SIZE & MAX. LENGTH |
8" - 70' |
8" - 80' |
10" - 100' |
10" - 120' |
| R/A SIZE NEEDED |
12" |
12" |
14" |
16" |
| MINIMUM OUTLETS2 |
14 |
20 |
30 |
40 |
| MAXIMUM OUTLETS |
20 |
29 |
45 |
50 |
E.W.T. Entering Water Temperature
E.S.P. External Static Pressure
G.P.M. Gallons Per Minute HP Horse Power MBH Thousand British Thermal Units per Hour RPM Revolutions Per Minute R/A Return Air S/A Supply Air TX Thermal Expansion
(1) Smaller condensers may be matched to the fancoil whenneeded (match TXV to condenser size)
(2) Minimum 8 full outlets per ton of cooling needed
ONE PHE 2-1/2" outlet is equal to TWO Standard 2" outlets. Read Addendum (pg ii) for more PHE Duct information.